Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 16, 2020, 09:21 AM
  • 22 0549_22 0548_10162020_023621.mp4

Date
10/16/2020
W/O
849889
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00791
PipeID
P16891
Time
2:21 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8162
Sewer Name
BEN LOMOND TRUNK
City
GLENDORA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
20
Purpose
Routine Assessment
Project
RFIR_WO_849889_TV22102_SEP2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
22 0549
Downstream MH
22 0548
Dir. of Survey
Downstream
Length Surveyed
292.1 ft.
Total Length
292.1 ft.
Structural Index
3
Structural Quick
3K2K
Structural Rating
290
O&M Index
2
O&M Quick
2K00
O&M Rating
116
Overall Index
2
Overall Quick
Overall Rating
406
Pipe schematic from manhole 22 0549 to 22 0548
MH: 22 0549MH: 22 0548downstream0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/OPEN0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 05490 ft. MGO - General Observation - ROACHES @ MH0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. MGO - General Observation - 65 % MAG COAT2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start53.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"61.7 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN132.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN177.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"181.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN268.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"276.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN290 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish290.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish290.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish292.1 ft. AMH - Downstream Manhole, Survey Ends - 22 0548292.1 ft. MGO - General Observation - ROACHES @ MH

Observation photos (2)

  • General Observation - ROACHES @ MH

    0 ft. - General Observation - ROACHES @ MH

  • General Observation - ROACHES @ MH

    292.1 ft. - General Observation - ROACHES @ MH

Observations (21)

DistanceCodeObservation
290.6SAP
0MGOCONN @ MH 9 O'CLOCK/OPEN
2DAGS
0MWL
61.7TBOPEN
2SAP
2MGO65 % MAG COAT
132.2TFOPEN
53.3TFC
276.7TFOPEN
290.6DAGS
292.1AMH22 0548
0AMH22 0549
2SSS
0MGOROACHES @ MH
0MWM
181.6TFOPEN
268.4TFA
290SSS
177.5TFA
292.1MGOROACHES @ MH

Properties (7)

additional_info
6301015200138P1
custom_field_three
PROJECTING AGGREGATE
custom_field_two
3
customer
1
datetime
2020-10-16T02:21:34-07:00
documentation
PRO PIPE
is_lateral_inspection
false