Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 2, 2020, 04:01 AM
  • C 0322_C 0321_10012020_211219.mp4

Date
10/01/2020
W/O
850057
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00136
PipeID
P09785
Time
9:01 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8106
Sewer Name
JOINT OUTFALL C - UNIT 6G
City
ARTESIA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
40
Purpose
Routine Assessment
Project
RFIR_WO_850057_TV02311_SEP2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
C 0322
Downstream MH
C 0321
Dir. of Survey
Downstream
Length Surveyed
72.3 ft.
Total Length
72.3 ft.
Structural Index
3
Structural Quick
5B3B
Structural Rating
146
O&M Index
2
O&M Quick
2B00
O&M Rating
28
Overall Index
3
Overall Quick
Overall Rating
174
Pipe schematic from manhole C 0322 to C 0321
MH: C 0322MH: C 0321downstream0 ft. AMH - Upstream Manhole, Survey Begins - C 03220 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - ROACHES @ MH2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start13.2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start13.2 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start53.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES70 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish70 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish72 ft. MGO - General Observation - ROACHES @ MH72 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish72.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish72.2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish72.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish72.3 ft. AMH - Downstream Manhole, Survey Ends - C 0321

Observation photos (4)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    13.2 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

    53.5 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (18)

DistanceCodeObservation
0AMHC 0322
53.5SAV
2SAV
72.2SAP
72.3AMHC 0321
2.2SSS
0MWL
13.2SRV
72MGOROACHES @ MH
72SRC
70SAV
70DAGS
72.2SRV
72.2SSS
0MWM
13.2SRC
2DAGS
0MGOROACHES @ MH

Properties (7)

additional_info
6301001200098P1
custom_field_three
AGGREGATE PROJECTING/REINFORCEMENT VISIBLE
custom_field_two
2
customer
1
datetime
2020-10-01T21:01:36-07:00
documentation
PROPIPE
is_lateral_inspection
false