Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 2, 2020, 04:25 AM
  • C 0320_C 0319_10012020_213640.mp4

Date
10/01/2020
W/O
850057
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00136
PipeID
P09783
Time
9:25 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8106
Sewer Name
JOINT OUTFALL C - UNIT 6G
City
ARTESIA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
40
Purpose
Routine Assessment
Project
RFIR_WO_850057_TV02311_SEP2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
C 0320
Downstream MH
C 0319
Dir. of Survey
Downstream
Length Surveyed
266.9 ft.
Total Length
266.9 ft.
Structural Index
3
Structural Quick
563J
Structural Rating
295
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
299
Pipe schematic from manhole C 0320 to C 0319
MH: C 0320MH: C 0319downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MGO - General Observation - ROACHES @ MH0 ft. AMH - Upstream Manhole, Survey Begins - C 03202 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3 ft. MGO - General Observation - 75% MAG COAT3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start250.7 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start250.7 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start264 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish266 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish266.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish266.9 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE266.9 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish266.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish266.9 ft. AMH - Downstream Manhole, Survey Ends - C 0319

Observation photos (3)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    250.7 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (17)

DistanceCodeObservation
0MWM
250.7SRC
0MWL
250.7SRV
266.9SSS
264DAGS
266.9MGOCONN @ MH 9 O'CLOCK/ACTIVE
3MGO75% MAG COAT
266.9SRV
2DAGS
0MGOROACHES @ MH
266.9SAV
266SRC
0AMHC 0320
2SSS
266.9AMHC 0319
3SAV

Properties (7)

additional_info
6301001200098P1
custom_field_three
REINFORCEMENT CORRODED/VISIBLE
custom_field_two
2
customer
1
datetime
2020-10-01T21:25:26-07:00
documentation
PROPIPE
is_lateral_inspection
false