Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 1, 2020, 05:09 PM
  • H 1341_B 0219 _10012020_102420.mp4

Date
10/01/2020
W/O
800065
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00085
PipeID
P08801
Time
10:09 AM
Certificate
U-109-7948
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8061
Sewer Name
JOINT OUTFALL B - UNIT 2B
City
EL MONTE
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
32
Purpose
Routine Assessment
Project
RFIR_WO_800065_TV15203_SEP2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
57 in.
Width
27 in.
Upstream MH
H 1341
Downstream MH
B 0219
Dir. of Survey
Downstream
Length Surveyed
202.6 ft.
Total Length
202.6 ft.
Structural Index
3
Structural Quick
593H
Structural Rating
187
O&M Index
2
O&M Quick
2G00
O&M Rating
80
Overall Index
3
Overall Quick
Overall Rating
267
Pipe schematic from manhole H 1341 to B 0219
MH: H 1341MH: B 0219downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 13410 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start16 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start154 ft. SRP - Surface Reinforcement Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES, Start154 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start200 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish200 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish200 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish200.6 ft. SRP - Surface Reinforcement Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish200.7 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish202.6 ft. AMH - Downstream Manhole, Survey Ends - B 0219

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    16 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    154 ft. - Surface Reinforcement Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

Observations (15)

DistanceCodeObservation
0MWL
202.6AMHB 0219
200.7SAV
200DAGS
2SSS
0MWM
200.6SRP
200SSS
0AMHH 1341
2DAGS
0MGOCONN @ MH 9 O'CLOCK/ACTIVE
200SRC
16SAV
154SRP
154SRC

Properties (7)

additional_info
6301001200066A1
custom_field_three
AGGREGATE VISIBLE/REINFIRCEMENT CORRODED
custom_field_two
3
customer
1
datetime
2020-10-01T10:09:03-07:00
documentation
PRO PIPE
is_lateral_inspection
false