- Date
- 10/27/2020
- W/O
- 0855542
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z00668
- PipeID
- P13747
- Time
- 2:39 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- H1598
- Sewer Name
- 17 DISTRICT #17 MAIN TRUNK
- City
- ALTADENA
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 17
- Page No.
- 06
- Purpose
- Maintenance Related
- Project
- 20201023MDM_DISTRICT_17_MAIN_TRUNK
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 15 in.
- Upstream MH
- 17 0023
- Downstream MH
- 17 0022
- Dir. of Survey
- Downstream
- Length Surveyed
- 360.7 ft.
- Total Length
- 360.7 ft.
- Structural Index
- 0
- Structural Quick
- 0000
- Structural Rating
- 0
- O&M Index
- 2
- O&M Quick
- 3321
- O&M Rating
- 16
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 16
Pipe schematic from manhole 17 0023 to 17 0022 Observation photos (4)

157.5 ft. - Roots Medium Connection, from 07 to 11 o'clock, 20 %, within 8 inches of joint: YES

331.5 ft. - Roots Medium Joint, from 12 to 04 o'clock, 25 %, within 8 inches of joint: YESR

360.1 ft. - General Observation - 3:00 SHELF SEVERE CORROSION

360.1 ft. - General Observation - 9:00 SHELF SEVERE CORROSION