Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 20, 2020, 04:52 PM
  • 1_1_1_20102020_111950.mp4

Date
10/20/2020
W/O
0853364
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00139
PipeID
P09813
Time
9:52 AM
Certificate
U-415-06024039
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0351
Sewer Name
JOINT OUTFALL C - UNIT 8A
City
LONG BEACH
Loc. details
Parking Lot
Location Code
G
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
09
Purpose
Capital Improvement Program Assesment
Project
20201020DF_JOINT_OUTFALL_C_UNIT_8A
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
42 in.
Width
15 in.
Upstream MH
C 0350
Downstream MH
C 0349
Dir. of Survey
Downstream
Length Surveyed
548.2 ft.
Total Length
548.5 ft.
Structural Index
4
Structural Quick
5g3U
Structural Rating
1535
O&M Index
2
O&M Quick
3E2U
O&M Rating
305
Overall Index
3
Overall Quick
Overall Rating
1840
Pipe schematic from manhole C 0350 to C 0349
MH: C 0350MH: C 0349downstream0 ft. AMH - Upstream Manhole, Survey Begins - 9:56 AM1 ft. MWM - Water Mark, 25 %of cross sectional area1 ft. MWL - Water Level, 20 %of cross sectional area1 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 0 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start100.7 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start340.2 ft. MGP - General Photograph403.4 ft. ID - Infiltration Dripper, at 12 o'clock, within 8 inches of joint: YES, Start403.4 ft. MGP - General Photograph548.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish548.2 ft. MSA - Survey Abandoned - ROPE SNAPPED548.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish548.2 ft. ID - Infiltration Dripper, at 12 o'clock, within 8 inches of joint: YES, Finish548.2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish548.2 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish548.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (8)

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 0 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 0 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    100.7 ft. - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Photograph

    340.2 ft. - General Photograph

  • Infiltration Dripper, at 12 o'clock, within 8 inches of joint: YES, Start

    403.4 ft. - Infiltration Dripper, at 12 o'clock, within 8 inches of joint: YES, Start

  • General Photograph

    403.4 ft. - General Photograph

Observations (19)

DistanceCodeObservation
2SRV
0AMH9:56 AM
2SSS
100.7SRC
1MWM
1MWL
403.4ID
548.2SAP
2DAGS
548.2MSAROPE SNAPPED
403.4MGP
548.2SSS
548.2ID
1MGOCONN @ MH 3 O'CLOCK/ACTIVE
340.2MGP
548.2SRV
548.2SRC
548.2DAGS
2SAP

Properties (5)

custom_field_two
5
customer
1
datetime
2020-10-20T09:52:10-07:00
documentation
FRANKLIN, SHADLER, IGNACIO, RAMIREZ, BRAR
is_lateral_inspection
false