Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 14, 2020, 08:32 AM
  • H 1413_H 1412 _09142020_015835.mp4

Date
09/14/2020
W/O
844678
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z01204
PipeID
P16284
Time
1:32 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8034
Sewer Name
JOINT OUTFALL H - UNIT 8M
City
WEST COVINA
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
30
Purpose
Routine Assessment
Project
WO_844678_TV22034_AUG2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
H 1413
Downstream MH
H 1412
Dir. of Survey
Downstream
Length Surveyed
259.2 ft.
Total Length
259.2 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole H 1413 to H 1412
MH: H 1413MH: H 1412downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 14130 ft. MWM - Water Mark, 25 %of cross sectional area2.1 ft. MGO - General Observation - MAG COAT30.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"55.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"79.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"110.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"142.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"158.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"214.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"248 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"258.9 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK259.2 ft. AMH - Downstream Manhole, Survey Ends - H 1412

Observations (14)

DistanceCodeObservation
79.8TFC
248TFC
55.7TFC
158.6TFC
0MWL
214.7TFC
0AMHH 1413
2.1MGOMAG COAT
30.3TFC
258.9MGOCONNECTION AT MH 9 O'CLOCK
142.8TFC
0MWM
259.2AMHH 1412
110.1TF

Properties (6)

additional_info
SC411847
custom_field_two
4
customer
1
datetime
2020-09-14T01:32:23-07:00
documentation
PRO PIPE
is_lateral_inspection
false