Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 14, 2020, 10:13 AM
  • H 1377_H 0624_09142020_032753.mp4

Date
09/14/2020
W/O
844678
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z01204
PipeID
P16252
Time
3:13 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8034
Sewer Name
JOINT OUTFALL H - UNIT 8M
City
west covina
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
30
Purpose
Routine Assessment
Project
WO_844678_TV22034_AUG2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
39 in.
Width
39 in.
Upstream MH
H 1377
Downstream MH
H 0624
Dir. of Survey
Downstream
Length Surveyed
474.2 ft.
Total Length
474.2 ft.
Structural Index
2
Structural Quick
2R00
Structural Rating
188
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
188
Pipe schematic from manhole H 1377 to H 0624
MH: H 1377MH: H 0624downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 13772 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start3.7 ft. MGO - General Observation - MAG COAT15.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"39.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"61.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"86.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"109.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"207.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"304.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"354 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"471 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish474.2 ft. AMH - Downstream Manhole, Survey Ends - H 0624

Observations (15)

DistanceCodeObservation
0MWL
474.2AMHH 0624
109.3TFC
471SSS
0MWM
354TFC
15.7TFC
86.2TFC
39.4TFC
207.1TFC
3.7MGOMAG COAT
2SSS
0AMHH 1377
61.8TFC
304.7TFC

Properties (6)

additional_info
SC411847
custom_field_two
4
customer
1
datetime
2020-09-14T03:13:52-07:00
documentation
PROPIPE
is_lateral_inspection
false