Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 15, 2019, 08:23 AM
  • 14 0209_14 0208 _10152019_014257.mp4

Date
10/15/2019
W/O
787624
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00584
PipeID
P18248
Time
1:23 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7037
Sewer Name
14 WEST SIDE TRUNK
City
LANCASTER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
18
Purpose
Routine Assessment
Project
RFIR_WO_787624_TV14035_SEP2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
14 0209
Downstream MH
14 0208
Dir. of Survey
Downstream
Length Surveyed
230.5 ft.
Total Length
230.5 ft.
Structural Index
3
Structural Quick
413H
Structural Rating
139
O&M Index
2
O&M Quick
2H11
O&M Rating
91
Overall Index
3
Overall Quick
Overall Rating
230
Pipe schematic from manhole 14 0209 to 14 0208
MH: 14 0209MH: 14 0208downstream0 ft. AMH - Upstream Manhole, Survey Begins - 14 02090 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start5.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start71.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"77.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"128.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"128.9 ft. FM - Fracture Multiple, from 12 to 05 o'clock, within 8 inches of joint: YES130.2 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"187.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"190.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"212 ft. RFJ - Roots Fine Joint, at 09 o'clock, within 8 inches of joint: YESR228.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish229 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish230.5 ft. AMH - Downstream Manhole, Survey Ends - 14 0208

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 12 to 05 o'clock, within 8 inches of joint: YES

    128.9 ft. - Fracture Multiple, from 12 to 05 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, at 09 o'clock, within 8 inches of joint: YESR

    212 ft. - Roots Fine Joint, at 09 o'clock, within 8 inches of joint: YESR

Observations (17)

DistanceCodeObservation
187.4TFA
190.1TFA
5.7CM
228.9CM
71.3TFA
2DAGS
212RFJ
130.2TFA
0AMH14 0209
128.9FM
230.5AMH14 0208
0MGOACTIVE CONNECTION AT MH 3 O'CLOCK
229DAGS
0MWL
0MWM
77.3TFA
128.5TFA

Properties (6)

additional_info
SC378706
custom_field_two
2
customer
LACSD
datetime
2019-10-15T01:23:48-07:00
documentation
PRO PIPE
is_lateral_inspection
false