Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 14, 2019, 09:17 AM
  • H 1390_H 1389 _08142019_022842.mp4

Date
08/14/2019
W/O
782286
Weather
Dry
Operator/Surveyor
J. VARGAS
Sewer ID
Z01204
PipeID
P16264
Time
2:17 AM
Certificate
U-209-8149
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6780
Sewer Name
H JOINT OUTFALL H - UNIT 8M
City
WEST COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
35
Purpose
Routine Assessment
Project
RFIR_WO_782286_TV22174_AUG2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
H 1390
Downstream MH
H 1389
Dir. of Survey
Downstream
Length Surveyed
146 ft.
Total Length
146 ft.
Structural Index
3
Structural Quick
3E2E
Structural Rating
140
O&M Index
2
O&M Quick
2E13
O&M Rating
59
Overall Index
2
Overall Quick
Overall Rating
199
Pipe schematic from manhole H 1390 to H 1389
MH: H 1390MH: H 1389downstream0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. VC - Vermin Cockroach0 ft. MWM - Water Mark, 45 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 13900 ft. MGO - General Observation - CONN 5 O'CLOCK @ MH/ACTIVE2 ft. VC - Vermin Cockroach, within 8 inches of joint: YES - @ MH4.7 ft. MGO - General Observation - 75% MAG COAT THROUGHOUT4.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start4.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start4.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start11.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"35.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"59.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN83.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"107.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"132.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"143.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish143.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish143.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish145 ft. VC - Vermin Cockroach, within 8 inches of joint: YES - @ MH146 ft. AMH - Downstream Manhole, Survey Ends - H 1389

Observation photos (4)

  • General Observation - 75% MAG COAT THROUGHOUT

    4.7 ft. - General Observation - 75% MAG COAT THROUGHOUT

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    4.7 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.7 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.7 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (21)

DistanceCodeObservation
4.7MGO75% MAG COAT THROUGHOUT
0MWL
2VC@ MH
0VC
0MWM
4.7DAGS
143.7SAP
0AMHH 1390
35.4TFC
4.7SAP
143.7SSS
107.7TFC
4.7SSS
145VC@ MH
83.3TFC
0MGOCONN 5 O'CLOCK @ MH/ACTIVE
11.2TFC
143.7DAGS
132.2TFC
59.2TFOPEN
146AMHH 1389

Properties (6)

additional_info
SC378286
custom_field_two
3
customer
LACSD
datetime
2019-08-14T02:17:58-07:00
documentation
PRO PIPE
is_lateral_inspection
false