Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 15, 2019, 05:41 AM
  • H 1387_H 1386 _08142019_225401.mp4

Date
08/14/2019
W/O
782286
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z01204
PipeID
P16260
Time
10:41 PM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6805
Sewer Name
H JOINT OUTFALL H - UNIT 8M
City
WEST COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
35
Purpose
Routine Assessment
Project
RFIR_WO_782286_TV22174_AUG2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
H 1387
Downstream MH
H 1386
Dir. of Survey
Downstream
Length Surveyed
75.9 ft.
Total Length
75.9 ft.
Structural Index
3
Structural Quick
3B2B
Structural Rating
70
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
70
Pipe schematic from manhole H 1387 to H 1386
MH: H 1387MH: H 1386downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 13872 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. MGO - General Observation - 80% MAG COAT THROUGHOUT21.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4", 10"45.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4", 4"69.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4", 8"73 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish73 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish75.9 ft. MGO - General Observation - CONN 3 O'CLOCK @ MH/ACTIVE75.9 ft. AMH - Downstream Manhole, Survey Ends - H 1386

Observation photos (5)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - 80% MAG COAT THROUGHOUT

    2 ft. - General Observation - 80% MAG COAT THROUGHOUT

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4", 10"

    21.6 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4", 10"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4", 4"

    45.3 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4", 4"

Observations (13)

DistanceCodeObservation
0MWM
0MWL
2SSS
21.6TFC
73SSS
73SAP
75.9MGOCONN 3 O'CLOCK @ MH/ACTIVE
45.3TFC
0AMHH 1387
75.9AMHH 1386
2SAP
69.9TFC
2MGO80% MAG COAT THROUGHOUT

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-08-14T22:41:32-07:00
documentation
PRO PIPE
is_lateral_inspection
false