Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 15, 2019, 05:56 AM
  • H 1386_H 1385 _08142019_231843.mp4

Date
08/14/2019
W/O
782286
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z01204
PipeID
P16259
Time
10:56 PM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6805
Sewer Name
H JOINT OUTFALL H - UNIT 8M
City
WEST COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
35
Purpose
Routine Assessment
Project
RFIR_WO_782286_TV22174_AUG2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
H 1386
Downstream MH
H 1385
Dir. of Survey
Downstream
Length Surveyed
328.6 ft.
Total Length
328.6 ft.
Structural Index
3
Structural Quick
3L2L
Structural Rating
320
O&M Index
2
O&M Quick
2700
O&M Rating
14
Overall Index
2
Overall Quick
Overall Rating
334
Pipe schematic from manhole H 1386 to H 1385
MH: H 1386MH: H 1385downstream0 ft. AMH - Upstream Manhole, Survey Begins - H 13860.1 ft. MWL - Water Level, 20 %of cross sectional area0.1 ft. MWM - Water Mark, 40 %of cross sectional area0.1 ft. MGO - General Observation - CONN 3 O'CLOCK @ MH/ACTIVE4.4 ft. MGO - General Observation - 85% MAG COAT THROUGHOUT4.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start4.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start17.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 8"41.8 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 8"65.7 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 8"90 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 8"122.7 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 8"154.6 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 8"210.4 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 8"234.7 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN258.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 10"282.5 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 8"306.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4", 8"326.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish326.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish328.6 ft. AMH - Downstream Manhole, Survey Ends - H 1385

Observation photos (9)

  • General Observation - 85% MAG COAT THROUGHOUT

    4.4 ft. - General Observation - 85% MAG COAT THROUGHOUT

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.4 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.4 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 8"

    65.7 ft. - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 8"

  • Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 8"

    90 ft. - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 8"

  • Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 8"

    154.6 ft. - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 8"

  • Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 8"

    210.4 ft. - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 8"

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN

    234.7 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN

  • Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 10"

    258.9 ft. - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 10"

Observations (21)

DistanceCodeObservation
4.4MGO85% MAG COAT THROUGHOUT
328.6AMHH 1385
122.7TBC
90TBC
4.4SAP
0.1MWL
234.7TBOPEN
0.1MWM
326.2SAP
326.2SSS
4.4SSS
258.9TFA
41.8TBC
65.7TBC
0AMHH 1386
282.5TBC
154.6TBC
210.4TBC
0.1MGOCONN 3 O'CLOCK @ MH/ACTIVE
306.4TFC
17.4TFC

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-08-14T22:56:22-07:00
documentation
PRO PIPE
is_lateral_inspection
false