Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 16, 2020, 10:05 AM
  • 18 0973_18 0972_10162020_031743.mp4

Date
10/16/2020
W/O
0855366
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00716
PipeID
P14825
Time
3:05 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1585R
Sewer Name
18 WORSHAM CREEK TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
11
Purpose
Maintenance Related
Project
20201016MDM_WORSHAM_CREEK_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
7.519999980926514 in.
Upstream MH
18 0973
Downstream MH
18 0972
Dir. of Survey
Downstream
Length Surveyed
394 ft.
Total Length
394 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
3211
O&M Rating
7
Overall Index
2
Overall Quick
Overall Rating
7
Pipe schematic from manhole 18 0973 to 18 0972
MH: 18 0973MH: 18 0972downstream0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 3:15AM0 ft. MWL - Water Level, 5 %of cross sectional area96.2 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: NO, 6" - Open98 ft. RMC - Roots Medium Connection, from 07 to 11 o'clock, 5 %, within 8 inches of joint: NO98 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: NO, 6" - Open191.2 ft. RFC - Roots Fine Connection, from 09 to 11 o'clock, within 8 inches of joint: NO - 4%191.2 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: NO, 6" - Active273.4 ft. TBD - Tap Break-In Defective, at 11 o'clock, -, , within 8 inches of joint: NO, 6" - Open-60% ROOTS394 ft. AMH - Downstream Manhole, Survey Ends - 3:50AM

Observations (11)

DistanceCodeObservation
96.2TBOpen
98RMC
273.4TBDOpen-60% ROOTS
0MGOConn. @ Mh, 9 O' Clock. Active
0MWM
191.2RFC4%
98TBOpen
0AMH3:15AM
394AMH3:50AM
191.2TBActive
0MWL

Properties (6)

additional_info
POAT ROOT EVALUATION ONLY
customer
LACSD
datetime
2020-10-16T03:05:29-07:00
documentation
MARTIN,OLIVER 111,RULVALCABA
is_lateral_inspection
false
lining
PVCP