Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 22, 2020, 05:03 PM
  • 21 0269B_21 0269A_09222020_100839.mp4

Date
09/22/2020
W/O
849680
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00763
PipeID
P15462
Time
10:03 AM
Certificate
U-109-7948
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8051
Sewer Name
DISTRICT #21 OUTFALL TRUNK
City
CITY OF INDUSTRY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 21
Page No.
28
Purpose
Routine Assessment
Project
WO_849680_TV21009_SEP2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
21 0269B
Downstream MH
21 0269A
Dir. of Survey
Downstream
Length Surveyed
24.4 ft.
Total Length
24.4 ft.
Structural Index
2
Structural Quick
2400
Structural Rating
8
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
8
Pipe schematic from manhole 21 0269B to 21 0269A
MH: 21 0269BMH: 21 0269Adownstream0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 21 0269B0 ft. MWL - Water Level, 35 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area2 ft. MGO - General Observation - MAG COAT START2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start20 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish20.8 ft. MGO - General Observation - MAG COAT END24.1 ft. AMH - Downstream Manhole, Survey Ends - 21 0269A24.4 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observations (11)

DistanceCodeObservation
2MGOMAG COAT START
0MGOCONNECTION AT MH 3 O'CLOCK
20.8MGOMAG COAT END
2SSS
0MGOCONNECTION AT MH 9 O'CLOCK
24.1AMH21 0269A
0AMH21 0269B
20SSS
24.4MGOCONNECTION AT MH 3 O'CLOCK
0MWL
0MWM

Properties (7)

additional_info
411349
custom_field_three
LIGHT GREASE
custom_field_two
3
customer
1
datetime
2020-09-22T10:03:34-07:00
documentation
PRO PIPE
is_lateral_inspection
false