Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 23, 2020, 04:35 PM
  • 21 0261_21 0260_09232020_104930.mp4

Date
09/23/2020
W/O
849680
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00763
PipeID
P15452
Time
9:35 AM
Certificate
U-109-7948
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8052
Sewer Name
DISTRICT #21 OUTFALL TRUNK
City
CITY OF INDUSTRY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 21
Page No.
36
Purpose
Routine Assessment
Project
WO_849680_TV21009_SEP2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
21 0261
Downstream MH
21 0260
Dir. of Survey
Downstream
Length Surveyed
391.2 ft.
Total Length
391.2 ft.
Structural Index
2
Structural Quick
2N00
Structural Rating
154
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
154
Pipe schematic from manhole 21 0261 to 21 0260
MH: 21 0261MH: 21 0260downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 21 02612 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. MGO - General Observation - MAG COAT start51.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 8"76.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"81.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"138.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"170.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6" - DEFECTED 100% FULL178.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6" - DEFECTED 100% FULL218.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6" - DEFECTED 100% FULL226.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6" - DEFECTED 100% FULL266.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6" - DEFECTED 100% FULL274.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4" - DEFECTED 100% FULL322.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4" - DEFECTED 100% FULL369.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4" - DEFECTED 100% FULL387 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish387.3 ft. MGO - General Observation - MAG COAT END391.2 ft. AMH - Downstream Manhole, Survey Ends - 21 0260

Observations (20)

DistanceCodeObservation
218.7TFCDEFECTED 100% FULL
0MWM
51.8TF
0MWL
178.2TFCDEFECTED 100% FULL
2SSS
170.5TFCDEFECTED 100% FULL
391.2AMH21 0260
369.3TFCDEFECTED 100% FULL
0AMH21 0261
76.8TF
138.2TFC
274.1TFCDEFECTED 100% FULL
387.3MGOMAG COAT END
81.7TFC
266.3TFCDEFECTED 100% FULL
387SSS
322.6TFCDEFECTED 100% FULL
2MGOMAG COAT start
226.3TFCDEFECTED 100% FULL

Properties (7)

additional_info
412001
custom_field_three
LIGHT GREASE
custom_field_two
3
customer
1
datetime
2020-09-23T09:35:43-07:00
documentation
PRO PIPE
is_lateral_inspection