Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 18, 2020, 05:14 AM
  • 08 0322_08 0321A_09172020_222056.mp4

Date
09/17/2020
W/O
849661
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00013
PipeID
P00370
Time
10:14 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8041
Sewer Name
KEYSTONE TRUNK
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_849661_TV08155_SEP2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
15 in.
Upstream MH
08 0322
Downstream MH
08 0321A
Dir. of Survey
Downstream
Length Surveyed
72.4 ft.
Total Length
72.4 ft.
Structural Index
3
Structural Quick
4B3B
Structural Rating
122
O&M Index
2
O&M Quick
2B00
O&M Rating
28
Overall Index
3
Overall Quick
Overall Rating
150
Pipe schematic from manhole 08 0322 to 08 0321A
MH: 08 0322MH: 08 0321Adownstream0 ft. AMH - Upstream Manhole, Survey Begins - 08 03220 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - ROACHES @ MH0 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start5.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start8.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish30.1 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"70 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish70 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish70 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish72 ft. MGO - General Observation - ROACHES @ MH72.4 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE72.4 ft. AMH - Downstream Manhole, Survey Ends - 08 0321A

Observation photos (1)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.1 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (17)

DistanceCodeObservation
72.4MGOCONN @ MH 3 O'CLOCK/ACTIVE
8.1FM
2DAGS
70SSS
0AMH08 0322
0MGOCONN @ MH 3 O'CLOCK/ACTIVE
72MGOROACHES @ MH
5.1FM
70CM
2SSS
70DAGS
0MWL
0MGOROACHES @ MH
72.4AMH08 0321A
0MWM
2CM
30.1TFC

Properties (7)

additional_info
SC411954
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2020-09-17T22:14:50-07:00
documentation
PROPIPE
is_lateral_inspection
false