Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 18, 2020, 06:32 AM
  • 08 0320_08 0319_09172020_234709.mp4

Date
09/17/2020
W/O
849661
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00013
PipeID
P00367
Time
11:32 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8041
Sewer Name
KEYSTONE TRUNK
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_849661_TV08155_SEP2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
15 in.
Upstream MH
08 0320
Downstream MH
08 0319
Dir. of Survey
Downstream
Length Surveyed
333.3 ft.
Total Length
333.3 ft.
Structural Index
3
Structural Quick
4L2L
Structural Rating
396
O&M Index
2
O&M Quick
2L00
O&M Rating
134
Overall Index
3
Overall Quick
Overall Rating
530
Pipe schematic from manhole 08 0320 to 08 0319
MH: 08 0320MH: 08 0319downstream0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE0 ft. MGO - General Observation - ROACHES @ MH0 ft. AMH - Upstream Manhole, Survey Begins - 08 03200 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start16.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"63 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"63.1 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES104.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"140.6 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN219 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN261.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"294.4 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"331 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish331 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish333 ft. MGO - General Observation - ROACHES @ MH333.3 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE333.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish333.3 ft. AMH - Downstream Manhole, Survey Ends - 08 0319

Observation photos (2)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 10 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES

    63.1 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES

Observations (22)

DistanceCodeObservation
0MGOCONN @ MH 9 O'CLOCK/ACTIVE
2DAGS
294.4TFC
16.9TFC
219TFOPEN
0MGOROACHES @ MH
63TFA
0AMH08 0320
2SSS
2FM
331DAGS
104.9TFC
261.9TFC
63.1DAGS
331SSS
333.3MGOCONN @ MH 3 O'CLOCK/ACTIVE
0MWL
333MGOROACHES @ MH
333.3FM
0MWM
140.6TFOPEN
333.3AMH08 0319

Properties (7)

additional_info
SC411954
custom_field_three
MULTIPLE CONTINUOUS FRACTURES THROUGHOUT
custom_field_two
2
customer
1
datetime
2020-09-17T23:32:35-07:00
documentation
PROPIPE
is_lateral_inspection
false