Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 25, 2020, 04:59 AM
  • 08 0312_08 0311_09242020_220929.mp4

Date
09/24/2020
W/O
849661
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00013
PipeID
P00359
Time
9:59 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8048
Sewer Name
KEYSTONE TRUNK
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_849661_TV08155_SEP2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
8 in.
Upstream MH
08 0312
Downstream MH
08 0311
Dir. of Survey
Downstream
Length Surveyed
278.9 ft.
Total Length
278.9 ft.
Structural Index
3
Structural Quick
4J36
Structural Rating
348
O&M Index
2
O&M Quick
2J00
O&M Rating
110
Overall Index
3
Overall Quick
Overall Rating
458
Pipe schematic from manhole 08 0312 to 08 0311
MH: 08 0312MH: 08 0311downstream0 ft. AMH - Upstream Manhole, Survey Begins - 08 03120 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start7.8 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN31 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish67 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 4" - UNKNOWN115.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"168 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 4" - UNKNOWN220.4 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN261.5 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"276 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish276 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish278 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE278 ft. MGO - General Observation - ROACHES @ MH278.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish278.9 ft. AMH - Downstream Manhole, Survey Ends - 08 0311

Observation photos (2)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (20)

DistanceCodeObservation
2FM
220.4TFOPEN
7.8TFOPEN
0AMH08 0312
278.9FM
2CM
261.5TFC
67TFUNKNOWN
2SSS
2DAGS
0MWL
115.3TFC
168TFUNKNOWN
276SSS
278MGOCONN @ MH 3 O'CLOCK/ACTIVE
278.9AMH08 0311
0MWM
31CM
278MGOROACHES @ MH
276DAGS

Properties (7)

additional_info
SC411961
custom_field_three
MULTIPLE FRACTURE'S
custom_field_two
2
customer
1
datetime
2020-09-24T21:59:13-07:00
documentation
PROPIPE
is_lateral_inspection
false