Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 17, 2020, 03:51 PM
  • _29 0285_09172020_091019.mp4

Date
09/17/2020
W/O
850185
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00375
PipeID
P24195
Time
8:51 AM
Certificate
U-109-7948
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7346
Sewer Name
ORANGE AVENUE SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
03
Purpose
Routine Assessment
Project
WO_850185_TV29040_SEP2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0285
Dir. of Survey
Upstream
Length Surveyed
312.2 ft.
Total Length
312.2 ft.
Structural Index
2
Structural Quick
312K
Structural Rating
127
O&M Index
2
O&M Quick
2L00
O&M Rating
126
Overall Index
2
Overall Quick
Overall Rating
253
Pipe schematic from manhole 29 0285 to unknown
MH: 29 0285MH: upstream0 ft. ACOM - Cleanout Mainline, Survey Ends0 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"2.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish2.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish35.2 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 4" - UNKNOWN38.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"40.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"57.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"66.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4" - OPEN120.8 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4", 4"137.3 ft. CM - Crack Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES147.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4" - OPEN188.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"246 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 4", 4" - 70% GREASE-LATERAL/OPEN251.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"305.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"310.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start310.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start312.2 ft. MWL - Water Level, 5 %of cross sectional area312.2 ft. AMH - Downstream Manhole, Survey Begins - 29 0285

Observation photos (1)

  • Crack Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES

    174.9 ft. - Crack Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES

Observations (20)

DistanceCodeObservation
312.2ACOM
271.9TFC
2DAGS
6.4TFA
2SSS
274.1TFC
66.2TFD70% GREASE-LATERAL/OPEN
310DAGS
123.3TFC
312.2TFA
0MWL
164.7TFOPEN
60.5TFA
277TFUNKNOWN
245.4TFOPEN
254.3TFC
0AMH29 0285
310SSS
191.4TFA
174.9CM

Properties (8)

additional_info
SC411345
custom_field_three
LIGHT GREASE CRACK
custom_field_two
3
customer
1
datetime
2020-09-17T08:51:25-07:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
39295