Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 16, 2020, 05:17 PM
  • 29 0281_29 0280_09162020_103051.mp4

Date
09/16/2020
W/O
850185
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00375
PipeID
P24190
Time
10:17 AM
Certificate
U-109-7948
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7344
Sewer Name
ORANGE AVENUE SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
01
Purpose
Routine Assessment
Project
WO_850185_TV29040_SEP2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0281
Downstream MH
29 0280
Dir. of Survey
Downstream
Length Surveyed
244.6 ft.
Total Length
244.6 ft.
Structural Index
2
Structural Quick
2I00
Structural Rating
98
O&M Index
2
O&M Quick
2I00
O&M Rating
96
Overall Index
2
Overall Quick
Overall Rating
194
Pipe schematic from manhole 29 0281 to 29 0280
MH: 29 0281MH: 29 0280downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 29 02812 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start35.3 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 4" - OPEN49.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"52.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"151 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"153.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"159.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"206.1 ft. FC - Fracture Circumferential, from 07 to 12 o'clock, within 8 inches of joint: YES242 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish242 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish244.6 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/OPEN244.6 ft. AMH - Downstream Manhole, Survey Ends - 29 0280

Observation photos (1)

  • Fracture Circumferential, from 07 to 12 o'clock, within 8 inches of joint: YES

    206.1 ft. - Fracture Circumferential, from 07 to 12 o'clock, within 8 inches of joint: YES

Observations (16)

DistanceCodeObservation
159.5TFA
244.6MGOCONN @ MH 9 O'CLOCK/OPEN
2DAGS
242DAGS
0MWL
151TFC
153.9TFC
244.6AMH29 0280
2SSS
52.6TFC
206.1FC
242SSS
0MWM
35.3TBOPEN
0AMH29 0281
49.5TFC

Properties (8)

additional_info
SC411343
custom_field_three
CIRCULARE FRACTURE
custom_field_two
2
customer
1
datetime
2020-09-16T10:17:45-07:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
39295