Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 9, 2020, 10:24 AM
  • 18 0973_18 0972_1092020_033013.mp4

Date
10/09/2020
W/O
0855366
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00716
PipeID
P14825
Time
3:24 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1585R
Sewer Name
18 WORSHAM CREEK TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
11
Purpose
Maintenance Related
Project
20201009MDM_WORSHAM_CREEK_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
7.519999980926514 in.
Upstream MH
18 0973
Downstream MH
18 0972
Dir. of Survey
Downstream
Length Surveyed
191.9 ft.
Total Length
191.9 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
4132
O&M Rating
10
Overall Index
3
Overall Quick
Overall Rating
10
Pipe schematic from manhole 18 0973 to 18 0972
MH: 18 0973MH: 18 0972downstream0 ft. AMH - Upstream Manhole, Survey Begins - 3:30AM0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area96 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6" - Active97.9 ft. TBD - Tap Break-In Defective, at 11 o'clock, -, , within 8 inches of joint: NO, 6" - Open-80% ROOTS190.8 ft. RBC - Roots Ball Connection, from 06 to 12 o'clock, 55 %, within 8 inches of joint: NO191.3 ft. TBD - Tap Break-In Defective, at 11 o'clock, -, , within 8 inches of joint: NO, 6" - Open-99% ROOTS191.9 ft. MSA - Survey Abandoned - 98% ROOTS

Observation photos (1)

  • Roots Ball Connection, from 06 to 12 o'clock, 55 %, within 8 inches of joint: NO

    190.8 ft. - Roots Ball Connection, from 06 to 12 o'clock, 55 %, within 8 inches of joint: NO

Observations (9)

DistanceCodeObservation
97.9TBDOpen-80% ROOTS
191.3TBDOpen-99% ROOTS
0AMH3:30AM
0MGOConn. @ Mh, 9 O' Clock. Active
191.9MSA98% ROOTS
96TBActive
190.8RBC
0MWM
0MWL

Properties (6)

additional_info
ROOT EVALUATION ONLY
customer
LACSD
datetime
2020-10-09T03:24:11-07:00
documentation
MARTIN, OLIVER III, CASTILLO
is_lateral_inspection
false
lining
PVCP