Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 22, 2020, 07:48 AM
  • C 0161_C 0160_09222020_010243.mp4

Date
09/22/2020
W/O
850193
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00129
PipeID
P09673
Time
12:48 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8047
Sewer Name
JOINT OUTFALL C - UNIT 5B
City
LONG BEACH
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
12
Purpose
Routine Assessment
Project
WO_850193_TV19024_SEP2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
42 in.
Upstream MH
C 0161
Downstream MH
C 0160
Dir. of Survey
Downstream
Length Surveyed
432.1 ft.
Total Length
432.1 ft.
Structural Index
3
Structural Quick
3P00
Structural Rating
258
O&M Index
2
O&M Quick
3223
O&M Rating
12
Overall Index
3
Overall Quick
Overall Rating
270
Pipe schematic from manhole C 0161 to C 0160
MH: C 0161MH: C 0160downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - C 01610 ft.0 ft. - 65% MAG COAT0 ft. MWL - Water Level, 20 %of cross sectional area2.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start108.3 ft. DAE - Deposits Attached Encrustation, 10 %of cross sectional area, from 12 to 04 o'clock, , within 8 inches of joint: YES209.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start209.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish254.4 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 01 to 04 o'clock, , within 8 inches of joint: YES285.4 ft. ID - Infiltration Dripper, from 01 to 05 o'clock, within 8 inches of joint: YES285.4 ft. DAE - Deposits Attached Encrustation, 15 %of cross sectional area, from 12 to 04 o'clock, , within 8 inches of joint: YES302 ft. DAE - Deposits Attached Encrustation, 10 %of cross sectional area, at 12 o'clock, , within 8 inches of joint: YES432 ft. MGO - General Observation - ROACHES @ MH432 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE432.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (6)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Encrustation, 10 %of cross sectional area, from 12 to 04 o'clock,  , within 8 inches of joint: YES

    108.3 ft. - Deposits Attached Encrustation, 10 %of cross sectional area, from 12 to 04 o'clock, , within 8 inches of joint: YES

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    209.5 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 01 to 04 o'clock,  , within 8 inches of joint: YES

    254.4 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 01 to 04 o'clock, , within 8 inches of joint: YES

  • Infiltration Dripper, from 01 to 05 o'clock, within 8 inches of joint: YES

    285.4 ft. - Infiltration Dripper, from 01 to 05 o'clock, within 8 inches of joint: YES

  • Deposits Attached Encrustation, 15 %of cross sectional area, from 12 to 04 o'clock,  , within 8 inches of joint: YES

    285.4 ft. - Deposits Attached Encrustation, 15 %of cross sectional area, from 12 to 04 o'clock, , within 8 inches of joint: YES

Observations (16)

DistanceCodeObservation
0MWM
302DAE
108.3DAE
2.1SAV
209.5SAP
0AMHC 0161
0
285.4ID
209.5SAV
432.1SAP
285.4DAE
254.4DAE
432MGOROACHES @ MH
065% MAG COAT
0MWL
432MGOCONN @ MH 9 O'CLOCK/ACTIVE

Properties (7)

additional_info
SC411960
custom_field_three
INFILTRATION DRIPPER/AGGREGATE PROJECTING
custom_field_two
2
customer
1
datetime
2020-09-22T00:48:15-07:00
documentation
PROPIPE
is_lateral_inspection
false