Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 22, 2020, 08:06 AM
  • C 0160_C 0159_09222020_011953.mp4

Date
09/22/2020
W/O
850193
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00129
PipeID
P09672
Time
1:06 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8047
Sewer Name
JOINT OUTFALL C - UNIT 5B
City
LONG BEACH
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
12
Purpose
Routine Assessment
Project
WO_850193_TV19024_SEP2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
42 in.
Upstream MH
C 0160
Downstream MH
C 0159
Dir. of Survey
Downstream
Length Surveyed
431.2 ft.
Total Length
431.2 ft.
Structural Index
3
Structural Quick
3P2P
Structural Rating
425
O&M Index
2
O&M Quick
312P
O&M Rating
177
Overall Index
2
Overall Quick
Overall Rating
602
Pipe schematic from manhole C 0160 to C 0159
MH: C 0160MH: C 0159downstream0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - C 01600 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.6 ft. MGO - General Observation - 70% MAG COAT72.6 ft. ID - Infiltration Dripper, at 12 o'clock, within 8 inches of joint: YES72.6 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, at 12 o'clock, , within 8 inches of joint: YES121.2 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 02 to 04 o'clock, , within 8 inches of joint: YES174.7 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"264.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN429 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish429 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish429 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish431.2 ft. AMH - Downstream Manhole, Survey Ends - C 0159

Observation photos (4)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Infiltration Dripper, at 12 o'clock, within 8 inches of joint: YES

    72.6 ft. - Infiltration Dripper, at 12 o'clock, within 8 inches of joint: YES

  • Deposits Attached Encrustation, 5 %of cross sectional area, at 12 o'clock,  , within 8 inches of joint: YES

    72.6 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, at 12 o'clock, , within 8 inches of joint: YES

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 02 to 04 o'clock,  , within 8 inches of joint: YES

    121.2 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 02 to 04 o'clock, , within 8 inches of joint: YES

Observations (17)

DistanceCodeObservation
2DAGS
0MGOCONN @ MH 9 O'CLOCK/ACTIVE
72.6ID
2SSS
0MWL
174.7TFA
431.2AMHC 0159
429SAV
3.6MGO70% MAG COAT
121.2DAE
2SAV
264.4TFOPEN
0AMHC 0160
72.6DAE
429DAGS
0MWM
429SSS

Properties (7)

additional_info
SC411960
custom_field_three
INFILTRATION DRIPPER/AGGREGATE VISIBLE
custom_field_two
2
customer
1
datetime
2020-09-22T01:06:07-07:00
documentation
PROPIPE
is_lateral_inspection
false