Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 17, 2020, 06:33 AM
  • E 0021_E 0126_09172020_002551.mp4

Date
09/16/2020
W/O
849880
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00027
PipeID
P23241
Time
11:33 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8039
Sewer Name
JOINT OUTFALL E - UNIT 1
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
20
Purpose
Routine Assessment
Project
RFIR_WO_849880_TV30070_SEP2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
42 in.
Width
42 in.
Upstream MH
E 0021
Downstream MH
E 0126
Dir. of Survey
Downstream
Length Surveyed
226.9 ft.
Total Length
226.9 ft.
Structural Index
3
Structural Quick
583H
Structural Rating
260
O&M Index
2
O&M Quick
2H00
O&M Rating
88
Overall Index
2
Overall Quick
Overall Rating
348
Pipe schematic from manhole E 0021 to E 0126
MH: E 0021MH: E 0126downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - E 00210 ft. MGO - General Observation - ROACHES @ MH2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start4.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start4.7 ft. MGO - General Observation - 75% MAG COAT224 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish224 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish224 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish224.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish226.4 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/226.9 ft. AMH - Downstream Manhole, Survey Ends - E 0126

Observation photos (1)

  • General Observation - 75% MAG COAT

    4.7 ft. - General Observation - 75% MAG COAT

Observations (15)

DistanceCodeObservation
226.4MGOCONN @ MH 9 O'CLOCK/
224SSS
224DAGS
0MWL
0MWM
2SRV
226.9AMHE 0126
4.7MGO75% MAG COAT
0AMHE 0021
2SSS
4.6SAP
224SRV
2DAGS
0MGOROACHES @ MH
224.3SAP

Properties (7)

additional_info
SC411951
custom_field_three
AGGREGATE PROJECTING
custom_field_two
3
customer
1
datetime
2020-09-16T23:33:19-07:00
documentation
PROPIPE
is_lateral_inspection
false