Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 17, 2020, 07:26 AM
  • E 0126_G 0094_09172020_003135.mp4

Date
09/17/2020
W/O
849880
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00027
PipeID
P07608
Time
12:26 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8039
Sewer Name
JOINT OUTFALL E - UNIT 1
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
20
Purpose
Routine Assessment
Project
RFIR_WO_849880_TV30070_SEP2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
42 in.
Width
15 in.
Upstream MH
E 0126
Downstream MH
G 0094
Dir. of Survey
Downstream
Length Surveyed
16.3 ft.
Total Length
16.3 ft.
Structural Index
3
Structural Quick
5232
Structural Rating
22
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
22
Pipe schematic from manhole E 0126 to G 0094
MH: E 0126MH: G 0094downstream0 ft. AMH - Upstream Manhole, Survey Begins - E 01260 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start11.1 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start15 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish16.3 ft. AMH - Downstream Manhole, Survey Ends - G 009416.3 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish16.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.9 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    11.1 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
16.3AMHG 0094
11.1SRV
15SSS
2SSS
16.3SRV
16.3SAP
0AMHE 0126
0MWM
3.9SAP
0MWL

Properties (7)

additional_info
SC411951
custom_field_three
AGGREGATE PROJECTING/REINFORCEMENT PROJECTING
custom_field_two
2
customer
1
datetime
2020-09-17T00:26:42-07:00
documentation
PROPIPE
is_lateral_inspection
false