Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 17, 2020, 05:19 AM
  • E 0022_E 0021_09162020_223131.mp4

Date
09/16/2020
W/O
849880
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00027
PipeID
P07603
Time
10:19 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8039
Sewer Name
JOINT OUTFALL E - UNIT 1
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
20
Purpose
Routine Assessment
Project
RFIR_WO_849880_TV30070_SEP2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
42 in.
Width
15 in.
Upstream MH
E 0022
Downstream MH
E 0021
Dir. of Survey
Downstream
Length Surveyed
411.3 ft.
Total Length
411.3 ft.
Structural Index
3
Structural Quick
513O
Structural Rating
413
O&M Index
2
O&M Quick
2O00
O&M Rating
162
Overall Index
2
Overall Quick
Overall Rating
575
Pipe schematic from manhole E 0022 to E 0021
MH: E 0022MH: E 0021downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - E 00210.1 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.1 ft. MGO - General Observation - 85% MAG COAT2.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start53.6 ft. SRV - Surface Reinforcement Visible, from 12 to 03 o'clock, within 8 inches of joint: YES218.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"409 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish409 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish411 ft. MGO - General Observation - ROACHES @ MH411.3 ft. AMH - Downstream Manhole, Survey Ends - E 0021411.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.3 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 12 to 03 o'clock, within 8 inches of joint: YES

    53.6 ft. - Surface Reinforcement Visible, from 12 to 03 o'clock, within 8 inches of joint: YES

Observations (14)

DistanceCodeObservation
2SSS
411.3AMHE 0021
411.3SAP
0.1MWM
53.6SRV
409SSS
218.5TFA
0MWL
411MGOROACHES @ MH
0AMHE 0021
2DAGS
409DAGS
2.1MGO85% MAG COAT
2.3SAP

Properties (7)

additional_info
SC411951
custom_field_three
AGGREGATE PROJECTING
custom_field_two
3
customer
1
datetime
2020-09-16T22:19:19-07:00
documentation
PROPIPE
is_lateral_inspection
false