Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 21, 2020, 11:41 AM
  • B 0959_B 0039_09212020_045117.mp4

Date
09/21/2020
W/O
850060
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00113
PipeID
P09420
Time
4:41 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8044
Sewer Name
JOINT OUTFALL B - UNIT 9A
City
COMPTON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
09
Purpose
Routine Assessment
Project
RFIR_WO_850060_TV08106_SEP2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
78 in.
Width
39 in.
Upstream MH
B 0959
Downstream MH
B 0039
Dir. of Survey
Downstream
Length Surveyed
29 ft.
Total Length
29 ft.
Structural Index
4
Structural Quick
5435
Structural Rating
35
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
35
Pipe schematic from manhole B 0959 to B 0039
MH: B 0959MH: B 0039downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 09592.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start24 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish26.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish29 ft. MGO - General Observation - DROP CONNECTION IN D/S MH @ 10 O'CLOCK29 ft. AMH - Downstream Manhole, Survey Ends - B 0039

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.2 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
0MWM
2.1SAP
0MWL
2.2SRV
24SRV
29MGODROP CONNECTION IN D/S MH @ 10 O'CLOCK
0AMHB 0959
26.4SAP
29AMHB 0039

Properties (7)

additional_info
SC411957
custom_field_three
AGGREGATE PROJECTING/REINFORCEMENT VISIBLE
custom_field_two
2
customer
1
datetime
2020-09-21T04:41:32-07:00
documentation
PROPIPE
is_lateral_inspection
false