Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 1, 2020, 08:01 AM
  • 05 1503_05 1502_10012020_012219.mp4

Date
10/01/2020
W/O
849606
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00497
PipeID
P06726
Time
1:01 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8104
Sewer Name
NORTH TORRANCE EXTENSION TRUNK
City
TORRANCE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
26
Purpose
Routine Assessment
Project
RFIR_WO_849606_TV05365_SEP2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
18 in.
Upstream MH
05 1503
Downstream MH
05 1502
Dir. of Survey
Downstream
Length Surveyed
336.6 ft.
Total Length
336.6 ft.
Structural Index
2
Structural Quick
2200
Structural Rating
4
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
4
Pipe schematic from manhole 05 1503 to 05 1502
MH: 05 1503MH: 05 1502downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 15030 ft. MWM - Water Mark, 30 %of cross sectional area28.4 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"51.5 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES77.4 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"126.9 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"178.7 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"226.5 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"274.2 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"323.7 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"330.2 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES336.6 ft. AMH - Downstream Manhole, Survey Ends - 05 1502

Observation photos (2)

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    51.5 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    330.2 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

Observations (13)

DistanceCodeObservation
51.5CL
336.6AMH05 1502
0MWL
0AMH05 1503
323.7TF
226.5TF
274.2TF
178.7TF
28.4TFA
126.9TF
0MWM
330.2CL
77.4TF

Properties (7)

additional_info
6301001200066P2
custom_field_three
RFIR NO SEVERE DEFECTS
custom_field_two
3
customer
1
datetime
2020-10-01T01:01:29-07:00
documentation
PROPIPE
is_lateral_inspection
false