- Date
- 09/22/2020
- W/O
- 849551
- Weather
- Dry
- Operator/Surveyor
- S. LOPEZ
- Sewer ID
- Z01133
- PipeID
- P13226
- Time
- 3:33 AM
- Certificate
- U-0720-70309212
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K8000
- Sewer Name
- JOINT OUTFALL B - UNIT 6L
- City
- ALHAMBRA
- Loc. details
- Main Highway - Urban
- Location Code
- A
- Use of Sewer
- Sanitary Sewer
- District
- District 16
- Page No.
- 20
- Purpose
- Routine Assessment
- Project
- RFIR_WO_849551_TV16108_SEP2020
- Sewer Type
- Gravity
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 21 in.
- Width
- 21 in.
- Upstream MH
- B 1138
- Downstream MH
- B 1255
- Dir. of Survey
- Downstream
- Length Surveyed
- 521.3 ft.
- Total Length
- 521.3 ft.
- Structural Index
- 3
- Structural Quick
- 5D3S
- Structural Rating
- 630
- O&M Index
- 2
- O&M Quick
- 2T00
- O&M Rating
- 208
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 838
Pipe schematic from manhole B 1138 to B 1255 Observation photos (5)

2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

12.1 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

12.1 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

12.1 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

521.3 ft. - General Observation - COCKROACHES AT MH