Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 18, 2020, 06:23 PM
  • C 0681_C 0680 _09182020_114339.mp4

Date
09/18/2020
W/O
849635
Weather
Dry
Operator/Surveyor
N.Zahreddine
Sewer ID
Z01114
PipeID
P23950
Time
11:23 AM
Certificate
U-1097948
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7347
Sewer Name
JOINT OUTFALL C - UNIT 3H
City
Signal Hill
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
01
Purpose
Routine Assessment
Project
WO_849635_TV29041_SEP2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
C 0681
Downstream MH
C 0680
Dir. of Survey
Downstream
Length Surveyed
110.8 ft.
Total Length
110.8 ft.
Structural Index
4
Structural Quick
5145
Structural Rating
25
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
25
Pipe schematic from manhole C 0681 to C 0680
MH: C 0681MH: C 0680downstream0 ft. AMH - Upstream Manhole, Survey Begins - C 06810 ft. MWL - Water Level, 0 %of cross sectional area0 ft. MWM - Water Mark, 5 %of cross sectional area3 ft. FM - Fracture Multiple, from 07 to 07 o'clock, within 8 inches of joint: YES, Start28.7 ft. FM - Fracture Multiple, from 07 to 07 o'clock, within 8 inches of joint: YES, Finish43.5 ft. B - Broken, from 10 to 02 o'clock, within 8 inches of joint: YES110.8 ft. AMH - Downstream Manhole, Survey Ends - C 0680

Observation photos (2)

  • Fracture Multiple, from 07 to 07 o'clock, within 8 inches of joint: YES, Start

    3 ft. - Fracture Multiple, from 07 to 07 o'clock, within 8 inches of joint: YES, Start

  • Broken, from 10 to 02 o'clock, within 8 inches of joint: YES

    43.5 ft. - Broken, from 10 to 02 o'clock, within 8 inches of joint: YES

Observations (7)

DistanceCodeObservation
110.8AMHC 0680
0AMHC 0681
43.5B
0MWL
3FM
28.7FM
0MWM

Properties (8)

additional_info
CS411346
custom_field_three
MULTIPLE FRACTURE/BROKEN PIPE
custom_field_two
2
customer
1
datetime
2020-09-18T11:23:50-07:00
documentation
ProPipe
is_lateral_inspection
false
year_laid
37482