Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 18, 2020, 02:02 PM
  • C 0678_C 0677 _09182020_072231.mp4

Date
09/18/2020
W/O
849635
Weather
Dry
Operator/Surveyor
N.Zahreddine
Sewer ID
Z01114
PipeID
P23947
Time
7:02 AM
Certificate
U-1097948
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7347
Sewer Name
JOINT OUTFALL C - UNIT 3H
City
Signal Hill
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
02
Purpose
Routine Assessment
Project
WO_849635_TV29041_SEP2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
C 0677
Downstream MH
C 0678
Dir. of Survey
Upstream
Length Surveyed
330.7 ft.
Total Length
330.7 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2L00
O&M Rating
132
Overall Index
2
Overall Quick
Overall Rating
135
Pipe schematic from manhole C 0677 to C 0678
MH: C 0677MH: C 0678upstream0 ft. AMH - Upstream Manhole, Survey Ends - C 06780 ft. MGO - General Observation - CONNECTION AT MH, 12 O'CLOCK0 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish88 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES175.3 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"294.9 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"330.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start330.7 ft. MWM - Water Mark, 30 %of cross sectional area330.7 ft. AMH - Downstream Manhole, Survey Begins - C 0677330.7 ft. MWL - Water Level, 10 %of cross sectional area

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    0 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    242.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (10)

DistanceCodeObservation
330.7AMHC 0678
0DAGS
155.4TF
0MWM
330.7MGOCONNECTION AT MH, 12 O'CLOCK
242.7CM
0AMHC 0677
35.8TF
0MWL
330.7DAGS

Properties (8)

additional_info
sc411346
custom_field_three
CRACK MULTIPLE
custom_field_two
4
customer
1
datetime
2020-09-18T07:02:35-07:00
documentation
ProPipe
is_lateral_inspection
false
year_laid
37482