Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 18, 2020, 02:34 PM
  • C 0677_C 0676 _09182020_075251.mp4

Date
09/18/2020
W/O
849635
Weather
Dry
Operator/Surveyor
N.Zahreddine
Sewer ID
Z01114
PipeID
P23946
Time
7:34 AM
Certificate
U-1097948
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7347
Sewer Name
JOINT OUTFALL C - UNIT 3H
City
Signal Hill
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
02
Purpose
Routine Assessment
Project
WO_849635_TV29041_SEP2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
C 0677
Downstream MH
C 0676
Dir. of Survey
Downstream
Length Surveyed
348.8 ft.
Total Length
348.8 ft.
Structural Index
4
Structural Quick
4L00
Structural Rating
260
O&M Index
2
O&M Quick
2M00
O&M Rating
138
Overall Index
3
Overall Quick
Overall Rating
398
Pipe schematic from manhole C 0677 to C 0676
MH: C 0677MH: C 0676downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - C 06770 ft. MWL - Water Level, 10 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Start22.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start82.7 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 4"219.1 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 4"275.6 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 4"281.3 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 4"338.4 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 4"348.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Finish348.8 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish348.8 ft. AMH - Downstream Manhole, Survey Ends - C 0676

Observation photos (1)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    22.7 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
0MWM
0AMHC 0677
348.8DAGS
281.3TB
2DAGS
348.8FM
275.6TBA
338.4TF
22.7FM
219.1TF
82.7TF
348.8AMHC 0676
0MWL

Properties (8)

additional_info
sc411346
custom_field_three
MULTIPLE FRACTURE
custom_field_two
3
customer
1
datetime
2020-09-18T07:34:13-07:00
documentation
ProPipe
is_lateral_inspection
false
year_laid
37482