Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 18, 2020, 03:10 PM
  • C 0676_C 0675 _09182020_082158.mp4

Date
09/18/2020
W/O
849635
Weather
Dry
Operator/Surveyor
N.Zahreddine
Sewer ID
Z01114
PipeID
P23945
Time
8:10 AM
Certificate
U-1097948
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7347
Sewer Name
JOINT OUTFALL C - UNIT 3H
City
Signal Hill
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
02
Purpose
Routine Assessment
Project
WO_849635_TV29041_SEP2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
C 0676
Downstream MH
C 0675
Dir. of Survey
Downstream
Length Surveyed
326.7 ft.
Total Length
326.7 ft.
Structural Index
3
Structural Quick
3J00
Structural Rating
165
O&M Index
2
O&M Quick
2L00
O&M Rating
128
Overall Index
2
Overall Quick
Overall Rating
293
Pipe schematic from manhole C 0676 to C 0675
MH: C 0676MH: C 0675downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - C 06762 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start43.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start94.5 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"253.6 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 4"319.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish323 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish326.7 ft. AMH - Downstream Manhole, Survey Ends - C 0675326.7 ft. MGO - General Observation - CONNECTION AT MH, 3 O'CLOCK

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    43.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
326.7AMHC 0675
94.5TF
319.2CM
2DAGS
0MWM
0MWL
323DAGS
326.7MGOCONNECTION AT MH, 3 O'CLOCK
0AMHC 0676
253.6TF
43.2CM

Properties (8)

additional_info
sc411346
custom_field_three
CRACK MULTIPLE
custom_field_two
3
customer
1
datetime
2020-09-18T08:10:48-07:00
documentation
ProPipe
is_lateral_inspection
false
year_laid
37482