Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 18, 2020, 06:02 PM
  • C 0672A_C 0672 _09182020_111140.mp4

Date
09/18/2020
W/O
849635
Weather
Dry
Operator/Surveyor
N.Zahreddine
Sewer ID
Z01114
PipeID
P23942
Time
11:02 AM
Certificate
U-1097948
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7347
Sewer Name
JOINT OUTFALL C - UNIT 3H
City
Signal Hill
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
02
Purpose
Routine Assessment
Project
WO_849635_TV29041_SEP2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
C 0672A
Downstream MH
C 0672
Dir. of Survey
Downstream
Length Surveyed
253.3 ft.
Total Length
253.3 ft.
Structural Index
4
Structural Quick
4I00
Structural Rating
192
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
192
Pipe schematic from manhole C 0672A to C 0672
MH: C 0672AMH: C 0672downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH, 9 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - C 0672A12.4 ft. FM - Fracture Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES15.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start89.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"192.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"250.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish253.3 ft. AMH - Downstream Manhole, Survey Ends - C 0672

Observation photos (2)

  • Fracture Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

    12.4 ft. - Fracture Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    15.6 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
0MWL
0MWM
0MGOCONNECTION AT MH, 9 O'CLOCK
12.4FM
192.5TF
253.3AMHC 0672
15.6FM
89.9TF
0AMHC 0672A
250.4FM

Properties (8)

additional_info
CS411346
custom_field_three
light grease
custom_field_two
4
customer
1
datetime
2020-09-18T11:02:23-07:00
documentation
ProPipe
is_lateral_inspection
false
year_laid
37482