Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 18, 2020, 07:00 PM
  • C 0679_C 0678A _09182020_121239.mp4

Date
09/18/2020
W/O
849635
Weather
Dry
Operator/Surveyor
N.Zahreddine
Sewer ID
Z01114
PipeID
P04935
Time
12:00 PM
Certificate
U-1097948
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7347
Sewer Name
JOINT OUTFALL C - UNIT 3H
City
Signal Hill
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
01
Purpose
Routine Assessment
Project
WO_849635_TV29041_SEP2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
30 in.
Upstream MH
C 0679
Downstream MH
C 0678A
Dir. of Survey
Downstream
Length Surveyed
294.5 ft.
Total Length
294.5 ft.
Structural Index
4
Structural Quick
5121
Structural Rating
7
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
7
Pipe schematic from manhole C 0679 to C 0678A
MH: C 0679MH: C 0678Adownstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - C 06790 ft. MGO - General Observation - CONNECTION AT MH, 9 O'CLOCK37 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 4"89.2 ft. FC - Fracture Circumferential, from 01 to 05 o'clock, within 8 inches of joint: YES168.1 ft. HSV - Hole Soil Visible, from 10 to 12 o'clock, within 8 inches of joint: YES - EXISTING HOLE170.3 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: NO, 4"294.5 ft. AMH - Downstream Manhole, Survey Ends - C 0678A294.5 ft. MGO - General Observation - CONNECTION AT MH, 3 O'CLOCK

Observation photos (2)

  • Fracture Circumferential, from 01 to 05 o'clock, within 8 inches of joint: YES

    89.2 ft. - Fracture Circumferential, from 01 to 05 o'clock, within 8 inches of joint: YES

  • Hole Soil Visible, from 10 to 12 o'clock, within 8 inches of joint: YES - EXISTING HOLE

    168.1 ft. - Hole Soil Visible, from 10 to 12 o'clock, within 8 inches of joint: YES - EXISTING HOLE

Observations (10)

DistanceCodeObservation
0MWL
294.5AMHC 0678A
0MWM
168.1HSVEXISTING HOLE
170.3TB
294.5MGOCONNECTION AT MH, 3 O'CLOCK
0AMHC 0679
0MGOCONNECTION AT MH, 9 O'CLOCK
89.2FC
37TB

Properties (8)

additional_info
CS411346
custom_field_three
HOLE IN THE PIPE
custom_field_two
1
customer
1
datetime
2020-09-18T12:00:30-07:00
documentation
ProPipe
is_lateral_inspection
false
year_laid
37482