Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 17, 2020, 09:26 AM
  • 32 1319_32 1318_09172020_023808.mp4

Date
09/17/2020
W/O
844702
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00843
PipeID
P19698
Time
2:26 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7996
Sewer Name
SOLEDAD CANYON RELIEF TRUNK
City
SANTA CLARITA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
11
Purpose
Routine Assessment
Project
WO_844702_TV32040_AUG2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
32 1318
Downstream MH
32 1319
Dir. of Survey
Upstream
Length Surveyed
62.1 ft.
Total Length
62.1 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
412A
O&M Rating
28
Overall Index
2
Overall Quick
Overall Rating
28
Pipe schematic from manhole 32 1318 to 32 1319
MH: 32 1318MH: 32 1319upstream0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Ends - 32 13191.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish60.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start62.1 ft. MWL - Water Level, 40 %of cross sectional area62.1 ft. MWM - Water Mark, 50 %of cross sectional area62.1 ft. AMH - Downstream Manhole, Survey Begins - 32 1318

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (7)

DistanceCodeObservation
62.1MGOCONNECTION AT MH 3 O'CLOCK
62.1AMH32 1319
60.8DAGS
2DAGS
0MWL
0MWM
0AMH32 1318

Properties (8)

additional_info
SC411888
custom_field_three
LIGHT GREASE
custom_field_two
4
customer
1
datetime
2020-09-17T02:26:00-07:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
32808