Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 4, 2020, 04:09 AM
  • 03 0227_03 0226_09032020_212520.mp4

Date
09/03/2020
W/O
844366
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00387
PipeID
P04828
Time
9:09 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8022
Sewer Name
NORTH LONG BEACH TRUNK
City
LONG BEACH
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
06
Purpose
Routine Assessment
Project
RFIR_WO_844366_TV03158_AUG2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
30 in.
Width
12 in.
Upstream MH
03 0227
Downstream MH
03 0226
Dir. of Survey
Downstream
Length Surveyed
434.7 ft.
Total Length
434.7 ft.
Structural Index
3
Structural Quick
3222
Structural Rating
10
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
10
Pipe schematic from manhole 03 0227 to 03 0226
MH: 03 0227MH: 03 0226downstream0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 03 02270 ft. MWM - Water Mark, 30 %of cross sectional area29.5 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES33.9 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES42.1 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES50.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start401.9 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ACTIVE434.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish434.7 ft. AMH - Downstream Manhole, Survey Ends - 03 0226

Observation photos (5)

  • Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    29.5 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    33.9 ft. - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    42.1 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    50.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ACTIVE

    401.9 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ACTIVE

Observations (10)

DistanceCodeObservation
50.1CM
42.1CL
401.9TBACTIVE
0MWL
434.7CM
29.5CM
434.7AMH03 0226
33.9CL
0AMH03 0227
0MWM

Properties (7)

additional_info
SC411835
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2020-09-03T21:09:50-07:00
documentation
PROPIPE
is_lateral_inspection
false