Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 17, 2020, 05:27 AM
  • 32 1161_32 1160_09162020_223139.mp4

Date
09/16/2020
W/O
844698
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00839
PipeID
P19615
Time
10:27 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7995
Sewer Name
SAN FERNANDO ROAD TRUNK
City
SANTA CLARITA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
09
Purpose
Routine Assessment
Project
RFIR_WO_844698_TV32021_AUG2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
32 1161
Downstream MH
32 1160
Dir. of Survey
Downstream
Length Surveyed
18.7 ft.
Total Length
18.7 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
3
O&M Quick
5141
O&M Rating
15
Overall Index
3
Overall Quick
Overall Rating
21
Pipe schematic from manhole 32 1161 to 32 1160
MH: 32 1161MH: 32 1160downstream0 ft. MWM - Water Mark, 75 %of cross sectional area0 ft. MWL - Water Level, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 32 11612 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: YES, Start6.6 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start18.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: YES, Finish18.7 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish18.7 ft. MSA - Survey Abandoned - DUE TO HIGH WATER LEVEL.18.7 ft. MCU - Camera Underwater

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    6.6 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
0MWM
18.7DAGS
18.7SAP
18.7MSADUE TO HIGH WATER LEVEL.
2DAGS
0MWL
6.6SAP
0AMH32 1161
18.7MCU

Properties (7)

additional_info
SC411887
custom_field_three
ABANDONED DUE TO WATER LEVEL. D/S IS SAUGUS WRP.
custom_field_two
5
customer
1
datetime
2020-09-16T22:27:21-07:00
documentation
PRO PIPE
is_lateral_inspection
false