Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 21, 2020, 05:05 AM
  • 29 0537_29 0454_08202020_222342.mp4

Date
08/20/2020
W/O
844690
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00537
PipeID
P24615
Time
10:05 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8003
Sewer Name
21ST STREET SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
03
Purpose
Routine Assessment
Project
RFIR_WO_844690_TV29055_AUG2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
29 0454
Downstream MH
29 0537
Dir. of Survey
Upstream
Length Surveyed
271.6 ft.
Total Length
271.6 ft.
Structural Index
3
Structural Quick
3J2J
Structural Rating
268
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
268
Pipe schematic from manhole 29 0454 to 29 0537
MH: 29 0454MH: 29 0537upstream0 ft. AMH - Upstream Manhole, Survey Ends - 29 05370.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish19.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN130.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"145.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"269.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start269.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start271.6 ft. AMH - Downstream Manhole, Survey Begins - 29 0454271.6 ft. MWL - Water Level, 5 %of cross sectional area271.6 ft. MGO - General Observation - ROACHES @ MH271.6 ft. MWM - Water Mark, 10 %of cross sectional area271.6 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
0AMH29 0454
0MWL
2SSS
0MGOROACHES @ MH
140.8TFC
126.4TFC
269SSS
271.6AMH29 0537
252.1TFOPEN
0MWM
271.5CM
0MGOCONN @ MH 9 O'CLOCK/ACTIVE
2CM

Properties (7)

additional_info
SC411815
custom_field_three
MULITIPLE CRACKS
custom_field_two
3
customer
1
datetime
2020-08-20T22:05:23-07:00
documentation
PROPIPE
is_lateral_inspection
false