Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 14, 2020, 09:27 AM
  • 32 0229_32 0163_09142020_023806.mp4

Date
09/14/2020
W/O
844413
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00891
PipeID
P19915
Time
2:27 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7987
Sewer Name
VALENCIA TRUNK
City
SANTA CLARITA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
08
Purpose
Routine Assessment
Project
RFIR_WO_844413_TV32044_AUG2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
32 0229
Downstream MH
32 0163
Dir. of Survey
Downstream
Length Surveyed
31.4 ft.
Total Length
31.4 ft.
Structural Index
3
Structural Quick
5535
Structural Rating
50
O&M Index
2
O&M Quick
4125
O&M Rating
14
Overall Index
3
Overall Quick
Overall Rating
64
Pipe schematic from manhole 32 0229 to 32 0163
MH: 32 0229MH: 32 0163downstream0 ft. AMH - Upstream Manhole, Survey Begins - 32 02290 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start28.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish28.7 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish28.7 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish29 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish31.4 ft. MGO - General Observation - ROACHES @ MANHOLE31.4 ft. AMH - Downstream Manhole, Survey Ends - 32 016331.4 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE

Observation photos (4)

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - ROACHES @ MANHOLE

    31.4 ft. - General Observation - ROACHES @ MANHOLE

Observations (14)

DistanceCodeObservation
0AMH32 0229
2SSS
2SAP
2SRC
0MWM
28.7DAGS
31.4MGOROACHES @ MANHOLE
28.7SAP
31.4AMH32 0163
0MWL
2DAGS
28.7SSS
31.4MGOCONN @ MH 3 O'CLOCK/ACTIVE
29SRC

Properties (8)

additional_info
SC411879
custom_field_three
VISIBLE REINFORCEMENT/PROJECTING AGGREGATE/SPALLIN
custom_field_two
2
customer
1
datetime
2020-09-14T02:27:50-07:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
26793