Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 6, 2020, 05:50 AM
  • 05 2225_05 2224_08052020_230828.mp4

Date
08/05/2020
W/O
844901
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00555
PipeID
P07549
Time
10:50 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7940
Sewer Name
SO HAWTHORNE-WARFIELD AV EXT RELF TR, SECTS 4B&4D
City
HAWTHORNE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
19
Purpose
Routine Assessment
Project
WO_844901_TV05274_AUG2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
24 in.
Upstream MH
05 2225
Downstream MH
05 2224
Dir. of Survey
Downstream
Length Surveyed
330.8 ft.
Total Length
330.8 ft.
Structural Index
2
Structural Quick
2L00
Structural Rating
130
O&M Index
2
O&M Quick
2L00
O&M Rating
130
Overall Index
2
Overall Quick
Overall Rating
260
Pipe schematic from manhole 05 2225 to 05 2224
MH: 05 2225MH: 05 2224downstream0 ft. AMH - Upstream Manhole, Survey Begins - 05 22250 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start214 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"328 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish328 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish330 ft. MGO - General Observation - ROACHES @ MH330.8 ft. AMH - Downstream Manhole, Survey Ends - 05 2224330.8 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE330.8 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE

Observation photos (1)

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    214 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

Observations (12)

DistanceCodeObservation
0AMH05 2225
328SSS
2DAGS
328DAGS
330MGOROACHES @ MH
214TB
330.8AMH05 2224
2SSS
0MWL
0MWM
330.8MGOCONN @ MH 3 O'CLOCK/ACTIVE
330.8MGOCONN @ MH 9 O'CLOCK/ACTIVE

Properties (8)

additional_info
SC411800
custom_field_three
SPALLING
custom_field_two
3
customer
1
datetime
2020-08-05T22:50:00-07:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
27103