Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 6, 2020, 07:10 AM
  • 05 2222_05 2221_08062020_002630.mp4

Date
08/06/2020
W/O
844901
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00555
PipeID
P07546
Time
12:10 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7940
Sewer Name
SO HAWTHORNE-WARFIELD AV EXT RELF TR, SECTS 4B&4D
City
HAWTHORNE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
19
Purpose
Routine Assessment
Project
WO_844901_TV05274_AUG2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
27 in.
Upstream MH
05 2222
Downstream MH
05 2221
Dir. of Survey
Downstream
Length Surveyed
323.8 ft.
Total Length
323.8 ft.
Structural Index
3
Structural Quick
3L2L
Structural Rating
320
O&M Index
2
O&M Quick
2L00
O&M Rating
128
Overall Index
2
Overall Quick
Overall Rating
448
Pipe schematic from manhole 05 2222 to 05 2221
MH: 05 2222MH: 05 2221downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 22222 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start321 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish321 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish321 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish323.8 ft. AMH - Downstream Manhole, Survey Ends - 05 2221

Observations (10)

DistanceCodeObservation
0MWM
2SSS
0MWL
2CM
2DAGS
321SSS
321DAGS
0AMH05 2222
321CM
323.8AMH05 2221

Properties (8)

additional_info
SC411800
custom_field_three
SPALLING
custom_field_two
3
customer
1
datetime
2020-08-06T00:10:00-07:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
27103