Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 9, 2020, 09:48 AM
  • 01 0214_01 0213_09092020_025426.mp4

Date
09/09/2020
W/O
844913
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00202
PipeID
P01256
Time
2:48 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8030
Sewer Name
COMPTON AVENUE TRUNK
City
los angeles
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
06
Purpose
Routine Assessment
Project
RFIR_WO_844913_TV01222_AUG2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
15 in.
Upstream MH
01 0214
Downstream MH
01 0213
Dir. of Survey
Downstream
Length Surveyed
159.4 ft.
Total Length
159.4 ft.
Structural Index
3
Structural Quick
3L2E
Structural Rating
256
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
256
Pipe schematic from manhole 01 0214 to 01 0213
MH: 01 0214MH: 01 0213downstream0 ft. MGO - General Observation - ROACHES @ MH0 ft. AMH - Upstream Manhole, Survey Begins - 01 02140 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. MGO - General Observation - 40% MAG COAT2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.2 ft. CL - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES2.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start132.8 ft. CM - Crack Multiple, from 07 to 02 o'clock, within 8 inches of joint: YES155.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES157 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish157 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish159 ft. MGO - General Observation - ROACHES @ MH159.4 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/UNKNOWN159.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish159.4 ft. AMH - Downstream Manhole, Survey Ends - 01 0213

Observation photos (4)

  • Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES

    2.2 ft. - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 07 to 02 o'clock, within 8 inches of joint: YES

    132.8 ft. - Crack Multiple, from 07 to 02 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    155.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (17)

DistanceCodeObservation
2.2CL
159.4MGOCONN @ MH 9 O'CLOCK/UNKNOWN
159.4SAV
159.4AMH01 0213
155.8CM
0MGOROACHES @ MH
132.8CM
157SSS
2MGO40% MAG COAT
0AMH01 0214
2CM
157CM
0MWM
2SSS
2.2SAV
0MWL
159MGOROACHES @ MH

Properties (7)

additional_info
SC411843
custom_field_three
MULTIPLE / AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2020-09-09T02:48:20-07:00
documentation
PROPIPE
is_lateral_inspection
false