Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 25, 2020, 07:27 AM
  • C 0108_C 0106_9252020_010528.mp4

Date
09/25/2020
W/O
0849527
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00123
PipeID
P09574
Time
12:27 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1571
Sewer Name
C JOINT OUTFALL C - UNIT 3D
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
20
Purpose
Routine Assessment
Project
20200923MDM_JOINT_OUTFALL_C_UNIT_3D
Material
Reinforced Concrete Pipe
Shape
Circular
Height
51 in.
Upstream MH
C 0108
Downstream MH
C 0106
Dir. of Survey
Downstream
Length Surveyed
553.5 ft.
Total Length
553.5 ft.
Structural Index
2
Structural Quick
2300
Structural Rating
6
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
8
Pipe schematic from manhole C 0108 to C 0106
MH: C 0108MH: C 0106downstream0 ft. AMH - Upstream Manhole, Survey Begins - 1:15AM0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. MGO - General Observation - MAG COAT 85% START11:00 TO 1:002 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE37.2 ft. SSS - Surface Spalling, from 11 to 01 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE UNDER MAG COAT221.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE553 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish553 ft. MGO - General Observation - MAG COAT 855 FINISH553 ft. MGO - General Observation - DEBRIE ON CABLE553 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERIMG PEELING CONCRETE553.5 ft. AMH - Downstream Manhole, Survey Ends - 1:50AM

Observation photos (6)

  • General Observation - MAG COAT 85% START11:00 TO 1:00

    2 ft. - General Observation - MAG COAT 85% START11:00 TO 1:00

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • Surface Spalling, from 11 to 01 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE UNDER MAG COAT

    37.2 ft. - Surface Spalling, from 11 to 01 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE UNDER MAG COAT

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE

    221.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE

  • General Observation - DEBRIE ON CABLE

    553 ft. - General Observation - DEBRIE ON CABLE

Observations (13)

DistanceCodeObservation
553DAGS
553.5AMH1:50AM
553MGOMAG COAT 855 FINISH
2MGOMAG COAT 85% START11:00 TO 1:00
2DAGS
37.2SSSBLISTERING PEELING CONCRETE UNDER MAG COAT
0AMH1:15AM
221.1SSSBLISTERING PEELING CONCRETE
553MGODEBRIE ON CABLE
2SSSBLISTERING PEELING CONCRETE
553SSSBLISTERIMG PEELING CONCRETE
0MWM
0MWL

Properties (6)

custom_field_three
BLISTERING PEELING CONCRETE
custom_field_two
4
customer
LACSD
datetime
2020-09-25T00:27:36-07:00
documentation
MARTIN,OLIVER 111,BARR,CASTILLO
is_lateral_inspection
false