Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 22, 2020, 07:28 AM
  • 02 1141_02 1140_9222020_002858.mp4

Date
09/22/2020
W/O
0849658
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00351
PipeID
P02924
Time
12:28 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1567
Sewer Name
02 GARFIELD AVENUE EXTENSION TRUNK
City
MONTEBELLO
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
13
Purpose
Maintenance Related
Project
20200921MDM_GARFIELD_AVENUE_EXTENSION_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
02 1141
Downstream MH
02 1140
Dir. of Survey
Downstream
Length Surveyed
316.7 ft.
Total Length
316.7 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2111
O&M Rating
3
Overall Index
2
Overall Quick
Overall Rating
3
Pipe schematic from manhole 02 1141 to 02 1140
MH: 02 1141MH: 02 1140downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 12:35AM25.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped74.1 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open76.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped127.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped178.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped178.1 ft. RFJ - Roots Fine Joint, from 02 to 04 o'clock, within 8 inches of joint: YESR - 2%229 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped249.8 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open-30% roots278.3 ft. MGO - General Observation - THIN NORMAL GREASE COAT316 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. STUB316 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active316.7 ft. AMH - Downstream Manhole, Survey Ends - 12:55AM

Observation photos (1)

  • General Observation - THIN NORMAL GREASE COAT

    278.3 ft. - General Observation - THIN NORMAL GREASE COAT

Observations (15)

DistanceCodeObservation
74.1TBOpen
229TFCCapped
249.8TFDOpen-30% roots
0MWL
25.5TFCCapped
316MGOConn. @ Mh, 3 O' Clock. STUB
178.1TFCCapped
0MWM
76.6TFCapped
178.1RFJ2%
127.4TFCCapped
316.7AMH12:55AM
316MGOConn. @ Mh, 9 O' Clock. Active
278.3MGOTHIN NORMAL GREASE COAT
0AMH12:35AM

Properties (5)

additional_info
POST CEANING EVALUATION ONLY
customer
LACSD
datetime
2020-09-22T00:28:18-07:00
documentation
MARTIN,OLIVER 111,BARR,CASTILLO
is_lateral_inspection
false