Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 12, 2020, 06:46 AM
  • 18 0816_18 0815_08122020_000455.mp4

Date
08/11/2020
W/O
844412
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00707
PipeID
P14679
Time
11:46 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7953
Sewer Name
SO WHITTIER OUTFALL TR, SECT 5
City
WHITTIER
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
20
Purpose
Routine Assessment
Project
RFIR_WO_844412_TV18119_AUG2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0816
Downstream MH
18 0815
Dir. of Survey
Downstream
Length Surveyed
210 ft.
Total Length
210 ft.
Structural Index
3
Structural Quick
554G
Structural Rating
397
O&M Index
2
O&M Quick
2H00
O&M Rating
88
Overall Index
3
Overall Quick
Overall Rating
485
Pipe schematic from manhole 18 0816 to 18 0815
MH: 18 0816MH: 18 0815downstream0 ft. MGO - General Observation - ROACHES @ MANHOLE0 ft. AMH - Upstream Manhole, Survey Begins - 18 08160 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start6.2 ft. CM - Crack Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES12.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES13.3 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"42 ft. B - Broken, from 12 to 04 o'clock, within 8 inches of joint: YES, Start57.4 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"68 ft. B - Broken, from 12 to 04 o'clock, within 8 inches of joint: YES, Finish109.4 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"207.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish207.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish208 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish208 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish210 ft. MGO - General Observation - ROACHES @ MANHOLE210 ft. AMH - Downstream Manhole, Survey Ends - 18 0815210 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE

Observation photos (6)

  • General Observation - ROACHES @ MANHOLE

    0 ft. - General Observation - ROACHES @ MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES

    6.2 ft. - Crack Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES

  • Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES

    12.5 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES

Observations (22)

DistanceCodeObservation
0MGOROACHES @ MANHOLE
2DAGS
6.2CM
68B
57.4TBC
208SSS
0AMH18 0816
0MWL
109.4TBC
207.6DAGS
210MGOROACHES @ MANHOLE
2FM
210AMH18 0815
208CM
2SSS
2CM
42B
207.6FM
12.5DAGS
13.3TBA
210MGOCONN @ MH 3 O'CLOCK/ACTIVE
0MWM

Properties (7)

additional_info
SC411743
custom_field_three
BROKEN PIPE/MULTIPLE FRACTURES
custom_field_two
1
customer
1
datetime
2020-08-11T23:46:49-07:00
documentation
PRO PIPE
is_lateral_inspection
false