Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 26, 2020, 09:35 AM
  • 30 0361_30 0360 _08262020_024527.mp4

Date
08/26/2020
W/O
844670
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00854
PipeID
P17997
Time
2:35 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8011
Sewer Name
CLIFTON P.P. FORCE MAIN GRAVITY TRUNK
City
REDONDO BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 30
Page No.
07
Purpose
Routine Assessment
Project
WO_844670_TV30011_AUG2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
30 0360
Downstream MH
30 0361
Dir. of Survey
Upstream
Length Surveyed
183 ft.
Total Length
183 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
1
O&M Quick
1300
O&M Rating
3
Overall Index
2
Overall Quick
Overall Rating
6
Pipe schematic from manhole 30 0360 to 30 0361
MH: 30 0360MH: 30 0361upstream0 ft. AMH - Upstream Manhole, Survey Ends - 30 03610 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish71.7 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start72 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"72 ft. RFC - Roots Fine Connection, at 10 o'clock141.6 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES142.1 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6"178.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start183 ft. MWM - Water Mark, 10 %of cross sectional area183 ft. AMH - Downstream Manhole, Survey Begins - 30 0360183 ft. MWL - Water Level, 5 %of cross sectional area

Observation photos (4)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6"

    40.9 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    111 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    111.3 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
111TB
111RFC
40.9TB
0MWM
183AMH30 0361
4.9CM
111.3RFJ
41.4RFJ
183CM
0AMH30 0360
183RFJ
0MWL

Properties (7)

additional_info
SC411823
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2020-08-26T02:35:26-07:00
documentation
PROPIPE
is_lateral_inspection
false