Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 26, 2020, 10:10 AM
  • 30 0358A_30 0358_08262020_032535.mp4

Date
08/26/2020
W/O
844670
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00854
PipeID
P17995
Time
3:10 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8011
Sewer Name
CLIFTON P.P. FORCE MAIN GRAVITY TRUNK
City
REDONDO BEACH
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 30
Page No.
07
Purpose
Routine Assessment
Project
WO_844670_TV30011_AUG2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
30 0358A
Downstream MH
30 0358
Dir. of Survey
Downstream
Length Surveyed
89.3 ft.
Total Length
89.3 ft.
Structural Index
3
Structural Quick
433B
Structural Rating
63
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
63
Pipe schematic from manhole 30 0358A to 30 0358
MH: 30 0358AMH: 30 0358downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 30 0358A2.1 ft. FM - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES4.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start10.6 ft. FM - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES72.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES89.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish89.3 ft. AMH - Downstream Manhole, Survey Ends - 30 0358

Observation photos (4)

  • Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES

    2.1 ft. - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES

    10.6 ft. - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    72.9 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (9)

DistanceCodeObservation
2.1FM
10.6FM
4.8CM
0MWL
0MWM
72.9FM
89.3CM
0AMH30 0358A
89.3AMH30 0358

Properties (7)

additional_info
SC411823
custom_field_three
FRACTURES
custom_field_two
2
customer
1
datetime
2020-08-26T03:10:22-07:00
documentation
PROPIPE
is_lateral_inspection
false