Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 2, 2020, 05:35 AM
  • 19 0223_19 0222_09012020_225043.mp4

Date
09/01/2020
W/O
844849
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00729
PipeID
P15192
Time
10:35 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7973
Sewer Name
WEST ARTESIA TRUNK
City
CERRITOS
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
04
Purpose
Routine Assessment
Project
WO_844849_TV19050_AUG2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
19 0223
Downstream MH
19 0222
Dir. of Survey
Downstream
Length Surveyed
368.5 ft.
Total Length
368.5 ft.
Structural Index
3
Structural Quick
3M2M
Structural Rating
360
O&M Index
2
O&M Quick
2N00
O&M Rating
152
Overall Index
2
Overall Quick
Overall Rating
512
Pipe schematic from manhole 19 0223 to 19 0222
MH: 19 0223MH: 19 0222downstream0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Begins - 19 02230 ft. MWL - Water Level, 15 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start6.2 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"6.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start6.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start78.8 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"159.7 ft. TBI - Tap Break-In Intruding, at 12 o'clock, -, -, within 8 inches of joint: NO, 1", 1", 6" - CAPPED232.2 ft. TBI - Tap Break-In Intruding, at 12 o'clock, -, #v, within 8 inches of joint: NO, 6", 1" - CAPPED304.9 ft. TBI - Tap Break-In Intruding, at 12 o'clock, -, -, within 8 inches of joint: NO, 1", 1", 6" - CAPPED366.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish366.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish366.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish368.5 ft. MGO - General Observation - COCKROACHES IN MANHOLE368.5 ft. AMH - Downstream Manhole, Survey Ends - 19 0222

Observation photos (6)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.8 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.8 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In Intruding, at 12 o'clock, -, #v, within 8 inches of joint: NO, 6", 1" - CAPPED

    232.2 ft. - Tap Break-In Intruding, at 12 o'clock, -, #v, within 8 inches of joint: NO, 6", 1" - CAPPED

  • General Observation - COCKROACHES IN MANHOLE

    368.5 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (18)

DistanceCodeObservation
0MGOCONNECTION AT MH 3 O'CLOCK
366.7SAP
0MWM
2DAGS
0MGOCOCKROACHES IN MANHOLE
159.7TBICAPPED
368.5MGOCOCKROACHES IN MANHOLE
368.5AMH19 0222
78.8TF
0AMH19 0223
0MWL
232.2TBICAPPED
304.9TBICAPPED
6.8SAP
366.7SSS
6.8SSS
366.7DAGS
6.2TFC

Properties (7)

additional_info
SC411864
custom_field_three
SPALLING/PROJECTING AGGREGATE
custom_field_two
3
customer
1
datetime
2020-09-01T22:35:45-07:00
documentation
PRO PIPE
is_lateral_inspection
false