Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 2, 2020, 04:34 AM
  • 08 0489_08 0488 _09012020_215540.mp4

Date
09/01/2020
W/O
845648
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00019
PipeID
P00547
Time
9:34 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8014
Sewer Name
SEPULVEDA-FIGUEROA STREET CONNECTING TRUNK
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
13
Purpose
Routine Assessment
Project
WO_845648_TV08028_AUG2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
48 in.
Upstream MH
08 0489
Downstream MH
08 0488
Dir. of Survey
Downstream
Length Surveyed
231.9 ft.
Total Length
231.9 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 08 0489 to 08 0488
MH: 08 0489MH: 08 0488downstream0 ft. MWM - Water Mark, 5 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 04895.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start22.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"69.8 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"76.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"125.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"190.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"217.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"228.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish231.9 ft. AMH - Downstream Manhole, Survey Ends - 08 0488

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    69.8 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

Observations (12)

DistanceCodeObservation
0MWM
0MWL
217.9TFC
76.6TF
190.2TFC
22.3TF
125.9TFC
5.7CM
231.9AMH08 0488
228.3CM
0AMH08 0489
69.8TB

Properties (7)

additional_info
SC411827
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2020-09-01T21:34:55-07:00
documentation
PROPIPE
is_lateral_inspection
false